Today I am sharing with new simple and easy 3 phase motor current calculation formula for LT motors. In this post, I am sharing with you a nameplate of 3 phase low voltage induction motor. In the nameplate, all data are given by the manufacturing companies.
In the below image I have shown a 3 phase motor nameplate. In the motor nameplate, the company provides the motor is 15 KW 3 phase induction motor. The Eff of the motor is 0.89 and PF is 0.85. The volts of the motor 380V and Amps are 30.1.
For 3 phase low voltage motor current calculation, we need the motor volts, Eff, PF. For three phase motor amps calculation, the below formula is used.
So our motor power is 15KW with 15 x 1000 = 15000 Watts. Motor volts are 380 volts, Eff is 0.89 and PF is 0.85 according to the above nameplate.
So if we calculate 15000/(1.732x380x0.85x0.89)
15000/(497.89) So 15000 / 497.89 = 30.12 Amps Or Load current of the motor.
By using this formula you can calculate the 3 phase low voltage motor. This is a very simple and easy formula.
3 Phase Motor Current Calculation Formula Explained
In the below image I have shown a 3 phase motor nameplate. In the motor nameplate, the company provides the motor is 15 KW 3 phase induction motor. The Eff of the motor is 0.89 and PF is 0.85. The volts of the motor 380V and Amps are 30.1.
So this data is provided by the company. Now first see the image and after that, we start doing the current calculation of 3 phase motor. That how comply calculate the current of three phase motor and how 30.1 amperes are given in nameplate.
For 3 phase low voltage motor current calculation, we need the motor volts, Eff, PF. For three phase motor amps calculation, the below formula is used.
3 phase motor current calculation formula is P/(√3xVxPfxEff) or P/(1.732xVxPfxEff) Both are the same.
So our motor power is 15KW with 15 x 1000 = 15000 Watts. Motor volts are 380 volts, Eff is 0.89 and PF is 0.85 according to the above nameplate.
So if we calculate 15000/(1.732x380x0.85x0.89)
15000/(497.89) So 15000 / 497.89 = 30.12 Amps Or Load current of the motor.
By using this formula you can calculate the 3 phase low voltage motor. This is a very simple and easy formula.
Also, read
Message:
I hope this 3 phase motor current calculation formula (how to calculate 3 phase motor current) help you. And know you will be able to calculate the load of 3 phase motor by using the above load current formula. Now if you have any questions or want to give us some suggestions about our blog then you can use the below comment section.
if possible write about formula or any calculation.
ReplyDeletehow to find suitable cable for load
please publish how to perform
ReplyDeleteshort circuit analysis
give us some formulae equation on amps voltage ampere if u have more give us to me pls tks
ReplyDeleteBe attaching the Circuits with videos please for better understanding.
ReplyDeleteExcellent
ReplyDeleteThank you sir for your effort teaching us online
ReplyDeletePlease tell me about calculation of overload setting.
ReplyDeleteexcellent
ReplyDeleteif p= power, pf=power factor, v=voltage, i=current, eff=?
ReplyDeleteEfficiency, which is 0.85%
DeletePls, how can we reverse single phase motor
ReplyDeleteThank u sir if u describe about the magnetic contractor overload relay and mccb breaker size calculation for dol and ster delta starter I will be happy
ReplyDelete